§ 5-1.3. Amendments to the 2013 California Residential Code  


Latest version.
  • a) R105.5 Expiration. Every permit issued shall become invalid unless the work authorized by such permit is commenced within 180 days after its issuance, or if the work authorized by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The building official is authorized to grant, in writing, one extension of time, for periods not more than 180 days. The extension shall be requested in writing and justifiable cause demonstrated. In order to renew action on a permit after expiration, the permittee shall pay a new full permit fee.

    b) R110.1 Use and occupancy. No building or structure shall be used or occupied, and no change in the existing occupancy classification of a building or structure or portion thereof shall be made until the building official has issued a certificate of occupancy therefore as provide herein. Issuance of a certificate of occupancy shall not be construed as an approval of a violation of the provisions of this code or of other ordinances of the jurisdiction. Certificate presuming to give authority to violate or cancel the provision of this code or other ordinances of jurisdiction shall not be valid.

    Exceptions:

    1. Certificates of occupancy are not required for work exempt from permits under Section R105.2.

    2. Accessory buildings or structures.

    3. Group R-3 and Group U Occupancies as defined in the California Building Code.

    c)

    TABLE R301.2(1)
    CLIMATIC AND GEOGRAPHIC DESIGN CRITERIA

    GROUND SNOW LOAD WIND DESIGN SEISMIC DESIGN CATEGORY SUBJECT TO DAMAGE FROM WINTER
    DESIGN
    TEMP
    ICE
    BARRIER
    UNDER-
    LAYMENT
    REQUIRED
    FLOOD HAZARDS AIR FREEZING INDEX;sup\sup; MEAN
    ANNUAL
    TEMP
    Speed (mph) Topographic effects Weathering Frost line Depth;sup\sup; Termite
    Zero 85 No D2 Negligible 12-24" Very Heavy 43 No See Footnote g 0 60

     

    For SI: 1 pound per square foot = 0.0479 kPa, 1 mile per hour = 0.447 m/s.

    a. Weathering may require a higher strength concrete or grade of masonry than necessary to satisfy the structural requirements of this code. The weathering column shall be filled in with the weathering index (i.e., "negligible," "moderate" or "severe") for concrete as determined from the Weathering Probability Map [Figure R301.2(3)]. The grade of masonry units shall be determined from ASTM C 34, C 55, C 62, C 73, C 90, C 129, C 145, C 216 or C 652.

    b. The frost line depth may require deeper footings than indicated in Figure R403.1(1). The jurisdiction shall fill in the frost line depth column with the minimum depth of footing below finish grade.

    c. The jurisdiction shall fill in this part of the table to indicate the need for protection depending on whether there has been a history of local subterranean termite damage.

    d. The jurisdiction shall fill in this part of the table with the wind speed from the basic wind speed map [Figure R30l.2(4)].Wind exposure category shall be determined on a site-specific basis in accordance with Section R301.2.1.4.

    e. Temperatures shall be permitted to reflect local climates or local weather experience as determined by the building official.

    f. The jurisdiction shall fill in this part of the table with the seismic design category determined from Section R301.2.2.1.

    g. The jurisdiction shall fill in this part of the table with (a) the date of the jurisdiction's entry into the National Flood Insurance Program (date of adoption of the first code or ordinance for management of flood hazard areas), (b) the date(s) of the Flood Insurance Study and (c) the panel numbers and dates of all currently effective FIRMs and FBFMs or other flood hazard map adopted by the authority having jurisdiction, as amended.

    (a) Date of initial ordinance, December 15, 1980.

    (b) Initial NFIP map date, May 17, 1974; initial FIRM date, September 30, 1982; most recent FIRM panel date, December 3. 2009.

    (c) Panels number 254, 258, 259, 262, 264, 266, 267, 268, 269, 278, 286.

    h. In accordance with Sections R905.2.7.1, R905.4.3.1, R905.5.3.1, R905.6.3.1, R905.7.3.1 and R905.8.3.1, where there has been a history of local damage from the effects of ice damming, the jurisdiction shall fill in this part of the table with "YES." Otherwise, the jurisdiction shall fill in this part of the table with "NO."

    i. The jurisdiction shall fill in this part of the table with the 100-year return period air freezing index (BF-days) from Figure R403.3(2) or from the 100-year (99%) value on the National Climatic Data Center data table "Air Freezing Index- USA Method (Base 32°)" at www.ncdc.noaa.gov/fpsf.htrnl.

    j. The jurisdiction shall fill in this part of the table with the mean annual temperature from the National Climatic Data Center data table "Air Freezing Index-USA Method (Base 32°F)" at www.ncdc.noaa.gov/fpsf.html.

    k. In accordance with Section R30 1.2.1.5, where there is local historical data documenting structural damage to buildings due to topographic wind speed-up effects, the jurisdiction shall fill in this part of the table with "YES." Otherwise, the jurisdiction shall indicate "NO" in this part of the table.

    (d) R902.1 Roofing covering materials. Roofs shall be covered with materials as set forth in Sections R904 and R905. A minimum Class A or B roofing shall be installed in areas designated by this section. Classes A or B roofing required by this section to be listed shall be tested in accordance with UL 790 or ASTM E 108.

    Exceptions:

    1. Class A roof assemblies include those with coverings of brick, masonry and exposed concrete roof deck.

    2. Class A roof assemblies also include ferrous or copper shingles or sheets, metal sheets and shingles, clay or concrete roof tile, or slate installed on noncombustible decks.

    3. Class A roof assemblies include minimum 16 oz/ftcopper sheets installed over combustible decks.

    (e) R902.1.3 Roof coverings within all other areas. The entire roof covering of every existing structure where more than 50 percent of the total roof area is replaced within any one-year period, the entire roof covering of every new structure, and any roof covering applied in the alteration, repair or replacement of the roof of every existing structure, shall be a fire-retardant roof covering that is at least Class B.

    (f) R902.2 Fire-retardant-treated shingles and shakes. Fire-retardant-treated wood shakes and shingles are wood shakes and shingles complying with UBC Standard 15-3 or 15-4 which are impregnated by the full-cell vacuum-pressure process with fire-retardant chemicals, and which have been qualified by UBC Standard 15-2 for use on Class A or B roofs.

    Fire-retardant-treated wood shakes and shingles shall comply with ICC-ES EG107 and with the weathering requirements contained in Health and Safety Code Section 13132.7(j). Each bundle shall bear labels from an ICBO accredited quality control agency identifying their roof-covering classification and indicating their compliance with ICC-ES EG107 and with the weathering requirements contained in Health and Safety Code Section 13132.7(j).

    Health and Safety Code Section 13132.7(j) No wood roof covering materials shall be sold or applied in this state unless both of the following conditions are met:

    (1) The materials have been approved and listed by the State Fire Marshal as complying with the requirements of this section.

    (2) The materials have passed at least five years of the 10-year natural weathering test. The 10-year natural weathering test required by this subdivision shall be conducted in accordance with Standard 15-2 of the 1994 edition of the Uniform Building Code at a testing facility recognized by the State Fire Marshal."

    (g) Amend item number 2 under "Building" in Section R105.2, Work exempt from permit, as follows:

    2. Wood, steel, vinyl, or iron fences not over 6 feet high. Stucco, concrete, brick, masonry, block fences not over 3 feet high.